The PDI PowerHub 2 PDU, by PDI, an Eaton Company, is a powerhouse unit and is available in sizes ranging from 375 – 1.25 MVA. The 60” wide x 40” deep, true, front-access cabinet is the smallest footprint in its class. Known for its centralized brazed bus system, the PowerHub 2 provides up to either (12) 400A or (16) 225A 100% rated, sub feed distribution breakers. It’s compartmentalized design isolates controls and high voltage components for simplified maintenance and increased operator safety. Front Access Infrared Scanning ensures maximum reliability and uptime for your mission critical facility. For proactive management of power usage and availability, the PowerHub 2 utilizes Intelligent Power Monitoring through the WaveStar® BCMS, or Branch Circuit Monitoring System including a class-leading 7” color touchscreen display.
PDI PowerHub 2 Features
- Four-tier True Front Access Cabinet: The 60″ wide x 40″ deep Four-tier True Front Access Cabinet maximizes square footage utilization and enables all operation, maintenance and service from the front of the PDU
- Front Access Infrared Scanning: Full swing out front doors and an unobstructed view cabinet design enable infrared scanning of all bolted line and load connections
- 375 to 1MVA DOE2016 Transformer: PowerHub 2 offers DOE-compliant transformers in sizes from 375 to 1MVA, up to 1.25 MVA High Efficiency Transformer
- Future-Proof Dual and Triple Output Transformer: PowerHub 2 offers dual and triple output transformers allowing easy migration to different voltages, future-proofing your data center
- Compartmentalized Controls & High Voltage Enclosures: Isolated compartments for both controls and high voltage components simplifies maintenance and increase operator safety
- Intelligent Power Monitoring: PDI’s Branch Circuit Monitoring System (BCMS) allows for the pro-active management of power usage and availability
- Brazed Transformer Connections: Brazed transformer connections decrease electrical resistance and eliminate the need for transformer infrared scanning
- Centralized Bus Design: PowerHub 2 provides up-to 12 (400A) and up-to 16 (225A) sub feed distribution breakers via a centralized bus design
- Adaptable Service Entrances: Landing service entrance cables has never been easier with Top/Bottom Entry/Exit configurations
PDI PowerHub 2 Specifications
kVA Rating | 375kVA – 1.25MVA |
Input | 3-phase, 3-wire plus ground |
Input Voltage | @ 50 Hz: 380V – 415V @ 60 Hz: 600, 480 or 208V |
Output | 3-phase, 4-wire plus ground |
Output Voltage | @ 50 Hz: 380/220, 400/231, 415/240VAC @ 60 Hz: 600/346, 575/332, 480/277, 415/240VAC or 208/120VAC |
Listed to UL | 1062, UL 1950, CSA Certified |
Operating Temperature | Ambient 0°C to 40°C |
Relative Humidity | 0% to 95% non-condensing |
Altitude | ≤ 6,600 ft. |
50 Hz Operating Range | 47-53 Hz |
60 Hz Operating Range | 57-63 Hz |
Storage Temperature | Ambient -10°C to +40°C |
For more in-depth specifications, see the data sheet.
For more information about PDI PowerHub 2,
call 86 21 5859 8677 or email sales@alphaenertech.com.