86 21 5859 8677

ASCO Series 300 Manual Transfer Switch with Integrated Quick-Connects (MTQ)

Power Distribution | ASCO Power Technologies | ASCO Power Transfer Switches | ASCO Series 300 Manual Transfer Switch with Integrated Quick-Connects (MTQ)

ASCO Series 300 Manual Transfer SwitchThe ASCO Series 300 Manual Transfer Switch with Integrated Quick-Connects (MTQ) provides a means for quickly connecting a portable or temporary generator to a building’s electrical system to provide backup power, or to provide a “backup to the backup” when servicing an off-line engine-generator. The Series 300 Manual Transfer Switch with Integrated Quick Connects provides a total temporary power connection and transfer solution that provides a complete UL 1008-listed solution in a single unit.

At facilities where backup power must be available, even when servicing a facility’s sole generator, National Electrical Code® Article 700.3(F) requires that a permanent switching means be provided to connect an interim source of secondary power. For facilities without a permanent backup generator, an MTS and a connecting means can facilitate the connection of a temporary or portable generator when needed, without the cost of a
permanent engine-generator.

ASCO Series 300 Manual Transfer Switch with Integrated Quick-Connects Features

  • Standard Type 3R cabinet is weatherproof with or without temporary power cables connected
  • Utilizes 16 Series Cam-Lok connectors
  • Simple and effective three position switch
  • Available from 150 to 3000 Amps, up to 600VAC, single or 3-phase
  • Standard Type 3R cabinet is weatherproof with or without temporary power cables connected
  • Modular, compact design is easy to install and maintain
  • Designed to handle the demands of motors and high inrush loads
  • Service Entrance configurations available
  • Utilizes 16 Series Cam type connectors
  • Leverages ASCO’s reliable, field-proven, transfer switching technology
  • Provides a complete UL1008 listed solution in a single unit; Larger amperage (1600A-3000A) MTQ listed under UL  891; Service Entrance (MUQ) configurations are listed under UL891 (TS is UL 1008)
  • Meets NFPA 110 standards for Emergency and Standby Power Systems and NEC® Article 700.3(F)

For more in-depth specifications, see the data sheet.

For more information about ASCO Power Technologies,
call 86 21 5859 8677 or email sales@alphaenertech.com.