The Newmar DIN Rail DC UPS, 12V, 24V and 48V DC, powers loads and charges the back-up battery and is ideal for security, wisp, wireless systems, transmitter and enclosure applications.
DIN Rail DC UPS Features
- Combines all system power functions: power supply, battery charger, UPS circuitry and status monitoring in one compact DIN rail mount unit
- Dual outputs for load and battery:
- “Load priority” output distribution ensures power is dedicated first to the load, with remainder then allocated to battery charging, thus preventing a discharged battery from impacting operation of critical loads.
- 3-step charging for rapid battery recovery, programmable for battery type, with optional temperature compensation sensor
- Battery automatically supports load anytime AC fails
- Low voltage disconnect prevents total battery discharge
- Operates from street light voltage – 277V AC
- Automatic periodic battery health diagnosis
- High operating temperature range to 70˚ C
- Alarm contacts: AC fail, battery at risk
- Communication MODBUS via RS-485 interface (DIN-UPS 48-10, DIN-UPS 24-20, and DIN-UPS 12-35 models only)
- CE Approved/Designed to UL 1950
DIN Rail DC UPS Specifications
Model | Output | MODBUS | Dimensions | Weight | |
---|---|---|---|---|---|
Voltage | Power | (H x W x D) | |||
DIN-UPS 12-10* | 12 VDC | 10 Amps | NA | 4.5″ x 2.6″ x 5.3″ | 2 Lbs. |
DIN-UPS 12-35 | 12 VDC | 35 Amps | Yes | 4.5″ x 5.9″ x 5.3″ | 4 Lbs. |
DIN-UPS 24-10 | 24 VDC | 10 Amps | NA | 4.5″ x 3.9″ x 5.3″ | 2 Lbs. |
DIN-UPS 24-20 | 24 VDC | 20 Amps | Yes | 4.5″ x 5.9″ x 5.3″ | 4 Lbs. |
DIN-UPS 48-5 | 48 VDC | 5 Amps | NA | 4.5″ x 3.9″ x 5.3″ | 2 Lbs. |
DIN-UPS 48-10 | 48 VDC | 10 Amps | Yes | 4.5″ x 5.9″ x 5.3″ | 4 Lbs. |
Additional Specifications
Front Panel LED Indicators: Power Source: AC or on back up and Battery and System Diagnostics (via blink code)
Settings/Selectors:
- Battery Type: Lead Acid, Gel-Cell
- Battery Charge Current Limit: 20 – 100% of charge amperage rating
- Back-Up Run Time on Batteries: Programmed time limit: 1 – 60 min. (DIN-UPS 48-10, DIN-UPS 24-20, and DIN-UPS 12-35 models only), or until LVD disconnect
- Power Restore Button: connects battery without AC present
Signal Outputs (form C):
- AC Fail – operating on back-up power
- Battery abnormal condition (summary contact): Discharged, damaged, disconnected, sulfated/ short circuit, reverse polarity, bad thermal sensor
- MODBUS Communication (DIN-UPS 48-10, DIN-UPS 24-20, and DIN-UPS 12-35 models only)
Temperature: -25 to +70˚ C. Continuous to 50˚, de-rate 2.5% per ˚C >50˚ C
Cooling: Free air, convection
Reliability (MTBF): 300,000 hours
Efficiency: 91%
Optional Accessories
- Battery temperature sensor: 100 feet or 3 foot cable lengths
- Parallel Connection for Redundancy: DIN-UPS units can be paralleled for 1+1 redundancy to obtain a higher system availability. Redundant systems require a certain amount of extra power to support the load in case one DIN-UPS unit fails. The simplest way is to put two DIN-UPS in parallel.