86 21 5859 8677

C&D UPS12-705PLMF

C&D UPS12-705PLMF Pure Lead MaxC&D UPS12-705PLMF Pure Lead Max Batteries, boast an industry leading 8-year warranty and 16 year design life and offers a sustainable, single-replacement for a 15-year UPS system. In addition to reducing the total cost of ownership, the Pure Lead Max offers verified safety, support for your sustainability initiatives, and reduces the system footprint. Pure Lead Max batteries are 98% recyclable and manufactured with up to 80% recycled materials. With no limitations on where it can be deployed, it is a flexible option.

Pure Lead Max has the same footprint as the C&D High Rate Max MR and Pure Lead Plus Series and can be a direct replacement for both. This makes it ideal for replacing a few batteries in an existing string without replacing the entire string. For more information see C&D High Rate Max MR Series and C&D Pure Lead Plus Series.

C&D UPS12-705PLMF Specifications

  • 12V 707 Watts/Cell @15 Min Rate
  • Dimensions (inches): 22 long x 4.9 deep x 12.7 high 
  • Weight: 142.0 lbs
  • 16 year design life
  • Terminal: Front

Operating Temperature Range: Discharge: -40°F (-40°C) to +160°F (+71°C) Charge: -10°F (-23°C) to +140°F (+60°C)
Nominal Operating Temperature Range: +74°F (+23°C) to +80°F (+27°C)
Recommended Maximum Charging Current Limit: C20/5 amperes (20 hr. rate)
Float Charge Voltage: 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger): 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20 (20 hr. rate)
Self Discharge: Batteries can be stored up to 24 months at +77°F (+25°C) before freshening charge is required. Batteries stored at temperatures greater than +77°F (+25°C) will require recharge sooner than batteries stored at lower temperatures.
Equalize and Cycle Service Charge Voltage: 14.40 to 14.80 VDC average per 12V unit @ +77°F (+25°C)
Terminal: Inserted:  Top Terminal Batteries: 1/4-20 UNC Bolt  Front Terminal Batteries: 1/4-20 UNC Bolt  / Insert (M8)
Terminal Hardware Initial Torque: Inserted
Terminal: Top Terminal Batteries: 110 in. lbs (12.4 N-m) Front Terminal Batteries 160 in. lbs (M8) or 110 in. lbs (1/4-206)

For more in-depth specifications, see the data sheet.

For more information about C&D Batteries,
call 86 21 5859 8677 or email sales@alphaenertech.com.