C&D UPS12-700MRF

The C&D Technologies UPS12-700MRF is a Valve Regulated Lead Acid (VRLA) Battery Series Designed for UPS Standby Power Applications.

C&D UPS12-700MRF Specifications

  • 12V 91 Watts / Cell @ 15 Min Rate
  • Dimensions (inches): 22 long x 4.95 wide x 12.60 high
  • Weight: 131 lbs / 60 Kg
  • 10 year design life @ 25C
  • Terminal: Insert

C&D UPS12-700MRF Features and Benefits

  • 10 Year Design Life @ 25°C
  • True Front Access threaded copper alloy inserts for reduced maintenance and increased safety.
  • Patented Long Life Alloy having the lowest calcium levels in the industry – minimizing grid growth, reducing gassing, and extending battery life.
  • Terminal versatility – ease of diagnostic readings with C&D Ohmic Ring®
  • Innovative front terminal design maximizing energy density with direct connect extrusion fusion weld technology.
  • Reduced headspace requirements resulting in higher energy density for cabinet or rack applications
  • Removable handles for ease of installation
  • Thermally welded case-to-cover bond to ensure a leak-proof seal.
  • Flame-retardant polypropylene case and cover compliant with UL94 V-0 with an Oxygen Limiting Index of greater than 28.
  • Absorbent Glass Mat (AGM) technology for efficient gas recombination of over 99%.
  • Flame-arresting, one-way pressure-relief vent for safety and long life.
  • Complies with UL1778, 924, 1989 and 94 V-0. BS6290-4, IEC-896-2.
  • UL-recognized component.
  • Multicell design for ease of installation and maintenance.
  • Not restricted for air transport – Complies with IATA/ICAO Special Provision A67.
  • Not restricted for surface transport – classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.
  • Not restricted for water transport – classified as non-hazardous material per Amendment 27.

UPS12-700MRF Additional Specifications

Operating Temperature Range with temperature compensation:
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range: +74°F (23°C) to +80°F (27°C)
Recommended Maximum Charging Current Limit: C20/5 amperes (35.2, 41.2)
Float Charging Voltage: 13.5 to 13.8 VDC average per 12V unit @ 77°F (25°C)
Maximum AC Ripple (Charger): 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.  Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C20/20
Equalize charge and cycle service voltage: 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal: Inserted – Inter-unit connector provided Threaded copper alloy insert terminal to accept 1/4-20 UNC bolt
Terminal Hardware: Torque 110 in.-lbs. (12.4 N-m)
Self Discharge: Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures.