86 21 5859 8677

C&D UPS12-1000MRXF

The C&D UPS12-1000MRXF Valve Regulated Lead Acid (VRLA) Battery Series is designed for UPS Standby Power Applications.

UPS12-1000MRXF Specifications

  • 12V 1000 Watts / Cell @ 15 Min Rate
  • Dimensions (inches): 22 long x 6.0 wide x 12.7 high
  • Weight: 188 lbs / 85.2 Kg
  • 10 year design life @ 25C
  • Terminal: Insert

C&D UPS12-1000MRXF Features & Benefits

  • True Front Access threaded copper alloy inserts for reduced maintenance and increased safety
  • Terminal versatility – ease of diagnostic readings with C&D Ohmic Ring
  • Innovative front terminal design maximizing energy density with direct connect extrusion fusion weld technology
  • Reduced headspace driving higher energy density, in cabinet or rack applications
  • Removable handles for ease of installation
  • Thermally welded case-to-cover bond to ensure a leak-proof seal
  • Patented Long Life Alloy having the lowest calcium levels in the industry – minimizing grid growth, reducing gassing, and extending battery life
  • Flame-retardant polypropylene case and cover compliant with UL94 V-0 with a Limiting Oxygen Index (LOI) of greater than 28
  • Absorbent Glass Mat (AGM) technology for efficient gas recombination of over 99%
  • Flame-arresting, one-way pressure-relief vent for safety and long life
  • Complies with UL1778, 924, 1989 and 94 V-0. BS6290-4, IEC-896-2
  • UL-recognized component
  • Multicell design for ease of installation and maintenance
  • Not restricted for air transport – Complies with IATA/ICAO Special Provision A67
  • Not restricted for surface transport – classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189
  • Not restricted for water transport – classified as non-hazardous material per Amendment 27

UPS12-1000MRXF Additional Specifications

Operating Temperature Range with temperature compensation:
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range: +74°F (23°C) to +80°F (27°C)
Recommended Maximum Charging Current Limit: C20/5 amperes
Float Charging Voltage: 13.5 to 13.8 VDC average per 12V unit @ 77°F (25°C)
Maximum AC Ripple (Charger): 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20 @ 20 Hr rate
Self Discharge: Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures.
Equalize charge and cycle service voltage: 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal: Inserted – Inter-unit connector provided: Threaded copper alloy insert terminal to accept: M6 bolt (UPS12-410MRXF) M8 bolt (UPS12-1000MRXF)
Terminal Hardware Initial Torque: 110 in.-lbs (12.4 N-m) for UPS12-410MRXF 160 in.-lbs. (18 N-m) for UPS12-1000MRXF

Weight: 188 pounds.

 

For more information about the High Rate Max Front Access Series,
call 86 21 5859 8677 or email sales@alphaenertech.com.