Introduction
This tech note helps answer, “How do I properly size my UPS?” by explaining the differences between Watts and VA and how the terms are correctly and incorrectly used in properly sizing UPS systems. Many people are confused about the distinction between the Watt and Volt-Amp (VA) measures for UPS load sizing. Many manufacturers of UPS and load equipment add to this confusion by failing to distinguish between these measures. If you have arrived at this site in an attempt to be a more informed buyer of UPS or other power equipment, congratulations. Please feel free to email us at sales@alphaenertech.com so that we may assist you in selecting the correct equipment. Alpha Ener Tech is an independent supplier of power quality products offering the best-in-class solutions.
Background
The power drawn by computing equipment is expressed in Watts or Volt-Amps (VA). The power in Watts is the real power drawn by the equipment. Volt-Amps are called the “apparent power” and are the product of the voltage applied to the equipment times the current drawn by the equipment. Both Watt and VA ratings have a use and purpose. The Watt rating determines the actual power purchased from the utility company and the heat loading generated by the equipment. The VA rating is used for sizing wiring and circuit breakers. The VA and Watt ratings for some types of electrical loads, like incandescent light bulbs, are identical. However, for computer equipment the Watt and VA ratings can differ significantly, with the VA rating always being equal to or larger than the Watt rating. The ratio of the Watt to VA rating is called the “Power Factor” and is expressed either as a number (i.e. 0.9) or a percentage (i.e. 90%). We can assist you with proper UPS sizing if you provide us with either, total equipment VA, total equipment Watts, or a list of the equipment part numbers that you would like to back up. Contact us at sales@alphaenertech.com to schedule a site survey.
The Watt rating for a computer may not be equal to the VA rating
All Information Technology equipment, including computers, uses an electronic switching power supply. There are two basic types of computer switching power supplies, which are called 1) Power Factor Corrected supplies or 2) Capacitor Input supplies. It is not possible to tell which kind of power supply is used by inspection of the equipment, and this information is not commonly provided in equipment specifications. Power Factor Corrected or PFC supplies were introduced in the mid 1990’s and have the characteristic that the Watt and VA ratings are equal (power factor of 0.99 to 1.0). Capacitor Input supplies have the characteristic that the Watt rating is in the range of .65 to .85 times the VA rating (power factor of 0.65 to 0.85).
All large computing equipment such as routers, switches, drive arrays, and servers made after about 1996 uses the Power Factor Corrected supply and consequently for this type of equipment the power factor is 1. Personal computers, small hubs, and personal computer accessories typically have Capacitor Input supplies and consequently for this type of equipment the power factor is less than one, and is ordinarily in the range of 0.65 to 0.85. Larger computer equipment made prior to 1996 also typically used this type of power supply and exhibited a power factor less than one.
The power rating of the UPS
UPS have both maximum Watt ratings and maximum VA ratings. Neither the Watt nor the VA rating of a UPS may be exceeded. It is a defacto standard in the industry that the Watt rating is approximately 60% of the VA rating for small UPS systems, this being the typical power factor of common personal computer loads. In some cases, UPS manufacturers only publish the VA rating of the UPS. For small UPS designed for computer loads, which have only a VA rating, it is appropriate to assume that the Watt rating of the UPS is 60% of the published VA rating. For larger UPS systems, it is becoming common to focus on the Watt rating of the UPS, and to have equal Watt and VA ratings for the UPS, because the Watt and VA ratings of the typical loads are equal.
In recent years, the major UPS manufacturers have been working to increase the efficiency of smaller UPS equipment. It has become more common to find single-phase UPS units with unity power factor – or power factor of 1.0. This is seen in 208V equipment more than 120V equipment. 120V operating voltages tend to remain in the .65 to .86 power factor range. As efficiency improves, the manufacturers are becoming better about publishing both a Watt and VA rating for any given model UPS. It is important to base sizing on the Watt rating of the UPS.
Examples where a sizing problem can occur
Example #1: Consider the case of a typical 1000VA UPS. The user wants to power a 900W heater with the UPS. The heater has a Watt rating of 900W and a VA rating of 900VA with a power factor of 1. Although the VA rating of the load is 900VA, which is within the VA rating of the UPS, the UPS will probably not power this load. That is because the 900W rating of the load exceeds the Watt rating of the UPS, which is most likely 60% of 1000VA or around 600W.
Example #2: Consider the case of a 1000VA UPS. The user wants to power a 900VA file server with the UPS. The file server has a Power Factor Corrected power supply, and so has a Watt rating of 900W and a VA rating of 900VA. Although the VA rating of the load is 900VA, which is within the VA rating of the UPS, the UPS will not power this load. That is because the 900W rating of the load exceeds the Watt rating of the UPS, which is 60% of 1000VA or around 600W.
How do I properly size my UPS and avoiding sizing errors
Equipment nameplate ratings are often in VA, which makes it difficult to know the Watt ratings. If using equipment nameplate ratings for sizing, a user might configure a system, which appears to be correctly sized based on VA ratings but actually exceeds the UPS Watt rating. By sizing the VA rating of a load to be no greater than 60% of the VA rating of the UPS, it is impossible to exceed the Watt rating of the UPS. Therefore, unless you have high certainty of the Watt ratings of the loads, the safest approach is to keep the sum of the load nameplate ratings below 60% of the UPS VA rating. Note that this conservative sizing approach will typically give rise to an oversized UPS and a larger run time than expected. If optimization of the system and an accurate run time are required, call our power experts who have the ability to accurately size your UPS. alphaenertech.com.
Conclusion
Power consumption information on computer loads is often not specified in a way that allows simple sizing of a UPS. It is possible to configure systems that appear to be correctly sized but actually overload the UPS. By slightly over sizing the UPS compared with the nameplate ratings of the equipment, proper operation of the system is ensured. Over sizing also provides the side benefit of providing additional UPS backup time. However, to truly ensure that your UPS is sized properly and that you do not waste money and space on an over-sized unit, contact us directly at sales@alphaenertech.com. Alpha Ener Tech has been helping clients select the correct UPS since 1996.